PHD ST2030

PHD ST2010

Description

Launched in 2005 and superseding the highly regarded PHD IP Series UPS, the T2 Series benefits from the latest microprocessor Control Unit (MCU) technology, and now offers even greater value for money. The T2 is aimed at users that require protection from line voltage fluctuations and require a reliable and constant power source. The T2 is a sophisticated unit utilizing full digital control technology. Available with power rating of 1kVA, 2kVA and 3kVA each with LCD display and audible alarm keeping you quickly updated on mains and battery status. The T2 is also fitted with an intelligent test button enabling a self-test routine which also prevents the UPS from being inadvertently switched off.

Features:

  • Extensive log files
  • Scheduled battery and inverter testing
  • Scheduled system shutdown/restart
  • User-Customisable commands and messages
  • Multiple UPS control from a single computer
  • Remote Console Command module for remote multiple server shutdown
  • Internal SNMP sub-agent for integration into existing NMS (e.g. HP OpenView, CA)

Specs:

Maximum Capacity 3000VA/2100W
Input Voltage Range 220/230/240VAC ± 25% Singe Phase w/Ground
Input Frequency 44Hz ~ 56Hz
Output Voltage 220/230/240VAC ± 2%
Output THD < 3%
Efficiency (Battery Mode) 82%
Output Frequency (Battery Mode) 50 ± 0.1Hz
Overload Capability (Normal Mode) Sustaining 5 min @ 100 – 200%; 3 sec @ > 200%
Overload Capability (Battery Mode) Sustaining 30 sec @ > 100%; 1 sec @ 150%
Number of Batteries 6 cells
Recharge Time to 90% < 8 hours (adjustable)
Charge Current of Long Standby Model * 10A
LCD AC Mode, Battery Mode, Output Status, Battery Capacity, Overload, UPS Fault
Battery Mode, Low Battery, Overload Long beeping, Continuous beeping, Short beeping
W × H × D (mm), Weight 220 × 330 × 487, 42kg
Operating Temperature -5 ~40°C
Relative Humidity < 95% (Non-Condensing)
Audible Noise <45dBA @ 1 meter